Intelligent Input/Output Module 956E
 Intelligent Input/Output Module 956E
Series : DC Powered
Spec : Intelligent I/O Module
Material : ABS
Color : White
Brand : ZOANCO
Model : 956E
Size : 86x86x28mm
Original : 0.00
Detail

I. Overview

The 956E Intelligent Input/Output Module(956E module for short) is used with MN300,atwo-bus linkage fire alarm control panel. It is mainly used to realize anoutput control for fire linkage equipment (such as smoke dampers, blow valvesand fire dampers) and receive the feedback signals of the fire linkageequipment so that a judgment on whether or not the fire linkage equipment isoperating normally can be done.

II.Features and technical parameters

1.     Mode of operation: Nonpolar two-wire system

2.     Quiescent current: 0.6mA(power-down mode)

3.     Action current: 10mA

4.     Capacity of the output control contact: 2A@DC30V

5.     Operation indicator: The inspection indicatorwill blink once about every 12 seconds in the inspection status or remain litin the output status; the input indicator will remain lit in the feedbackstatus.

6.     Operatingenvironment: Temperature: 10℃50℃; relativehumidity: ≤95% (40℃±2℃, withoutcondensation)

7.     Terminal load: 47K resistance

8.     External dimensions: 86×86×40(mm)

9.     Weight: about 130g

10.   Executive standard: GB16806-2006

III.Instructions for use

11.   Terminal description for the CFT-956 module

Terminal description (see Fig.2)

Terminal No.

Function

Mode of the built-in  terminal load (factory default)

Mode of the external  terminal load

1

+24V

-------- (strictly  prohibited)

DC24V access terminal (positive)

2

GND

Normally open contact (closed after action)

DC24V access terminal (negative)

3

TO0

Public contact

Load access terminal (negative)

4

TO1

-------- (strictly prohibited)

Load access terminal (positive)

5

TO2

Normally closed contact (open after action)

-------- (strictly prohibited)

7

FB0

Access terminal for the feedback signals of the fire  linkage equipment

8

FB1

Access terminal for the feedback signals of the fire  linkage equipment

9

L1

Access terminal for the bus signal of the linkage fire  alarm control panel

10

L2

Access terminal for the bus signal of the linkage fire  alarm control panel

Jumper description (see Fig.1)

Jumper

Pins 1 and 2 shorted

Pins 2 and 3 shorted

JP1,JP2 and JP3

External terminal load

Built-in terminal load (factory default)

JP4

Normal mode

Power-down mode (factory default)