I. Overview
The 956E Intelligent Input/Output Module(956E module for short) is used with MN300,atwo-bus linkage fire alarm control panel. It is mainly used to realize anoutput control for fire linkage equipment (such as smoke dampers, blow valvesand fire dampers) and receive the feedback signals of the fire linkageequipment so that a judgment on whether or not the fire linkage equipment isoperating normally can be done.
II.Features and technical parameters
1. Mode of operation: Nonpolar two-wire system
2. Quiescent current: <0.6mA(power-down mode)
3. Action current: <10mA
4. Capacity of the output control contact: 2A@DC30V
5. Operation indicator: The inspection indicatorwill blink once about every 12 seconds in the inspection status or remain litin the output status; the input indicator will remain lit in the feedbackstatus.
6. Operatingenvironment: Temperature: -10℃~50℃; relativehumidity: ≤95% (40℃±2℃, withoutcondensation)
7. Terminal load: 47K resistance
8. External dimensions: 86×86×40(mm)
9. Weight: about 130g
10. Executive standard: GB16806-2006
III.Instructions for use
11. Terminal description for the CFT-956 module
Terminal description (see Fig.2)
Terminal No. | Function | Mode of the built-in terminal load (factory default) | Mode of the external terminal load |
1 | +24V | -------- (strictly prohibited) | DC24V access terminal (positive) |
2 | GND | Normally open contact (closed after action) | DC24V access terminal (negative) |
3 | TO0 | Public contact | Load access terminal (negative) |
4 | TO1 | -------- (strictly prohibited) | Load access terminal (positive) |
5 | TO2 | Normally closed contact (open after action) | -------- (strictly prohibited) |
7 | FB0 | Access terminal for the feedback signals of the fire linkage equipment |
8 | FB1 | Access terminal for the feedback signals of the fire linkage equipment |
9 | L1 | Access terminal for the bus signal of the linkage fire alarm control panel |
10 | L2 | Access terminal for the bus signal of the linkage fire alarm control panel |
Jumper description (see Fig.1)
Jumper | Pins 1 and 2 shorted | Pins 2 and 3 shorted |
JP1,JP2 and JP3 | External terminal load | Built-in terminal load (factory default) |
JP4 | Normal mode | Power-down mode (factory default) |